Network Configuration

  • Maximum Network Length and Drop Line Length
    Check that the cables used on the network meet the following specifications.

    Wire Type Baud Rates Max. Network Length Drop Line Length Total Drop Line Length
    Thick Cable 500 kbps 100 m 6 m 39 m
    250 kbps 250 m 78 m
    125 kbps 500 m 156 m
    Thin Cable 500 kbps 100 m 39 m
    250 kbps 100 m 78 m
    125 kbps 100 m 156 m
  1. Terminating Resistor
    Ensure that two terminating resistors are connected to both ends of the network (trunk line).
    The terminating resistor should be 121 Ω 1/4 W.

  2. Cable and Branch Tap
    The cables and branch taps should meet the DeviceNet specifications.

  3. Communications Power Supply
    The communications power supply should be dedicated to DeviceNet.
    Do not share the communications power supply with I/O devices.*
    *Noise due to load on/off may affect DeviceNet communications via the communications power supply.
    (The noise causes remote I/O communication error, Busoff detection, and broken unit.)