Network Configuration
Max. Cable Length
Check that the cables used on the network meet the following specifications.
Baud Rates Max. Cable Length 12 Mbps 100 m 6 Mbps 100 m 3 Mbps 100 m 1500 kbps 200 m 500 kbps 400 m 187.5 kbps 1000 m 93.75 kbps 1200 m 19.2 kbps 1200 m 9.6 kbps 1200 m Terminating Resistor
Ensure that two terminating resistors are connected to both ends of the network.
The terminating resistor should be connected as shown below.
Symbol Description a Data line A b Data line B Cable
The cables should meet the PROFIBUS specifications.
Item Property Impedance 135 to 165 Ω Capacity < 30 pf/m Loop resistance 110 Ω/km Wire diameter 0.64 mm Core cross-section > 0.34 mm2