Network Configuration

  • Max. Cable Length

    Check that the cables used on the network meet the following specifications.

    Baud Rates Max. Cable Length
    12 Mbps 100 m
    6 Mbps 100 m
    3 Mbps 100 m
    1500 kbps 200 m
    500 kbps 400 m
    187.5 kbps 1000 m
    93.75 kbps 1200 m
    19.2 kbps 1200 m
    9.6 kbps 1200 m
  • Terminating Resistor

    Ensure that two terminating resistors are connected to both ends of the network.

    The terminating resistor should be connected as shown below.

    Symbol Description
    a Data line A
    b Data line B
  • Cable

    The cables should meet the PROFIBUS specifications.

    Item Property
    Impedance 135 to 165 Ω
    Capacity < 30 pf/m
    Loop resistance 110 Ω/km
    Wire diameter 0.64 mm
    Core cross-section > 0.34 mm2