Code Number 1 ~

No. Message Remedy Note 1 Note 2
1 Controller control program started. -
2 Termination due to low voltage of the power supply. -
3 Controller control program has completed. Stores this log when the controller is rebooted from Epson RC+ or TP1.
4 Preserve variables save area has been cleaned. -
5 Function Main started. -
6 Function Main started. Later same logs are skipped. Skip the log "Function Main started." to prevent system history space run out.
7 Serial number has been saved. -
8 System backup has been executed. -
9 System restore has been executed. -
10 Robot parameters have been initialized. -
11 Offset pulse value between the encoder origin and the home sensor (HOFS) is changed. - Value after change Value before change
17 Message saving mode activated. -
18 Conversion of Robot Parameter file has been executed. -
19 DU firmware has been installed. -
20 Enable setting in Teach mode has been saved. -
21 Enable setting in Teach mode has been changed. -
23 EStop has been executed. - Robot number executing motion command Controller status
24 Safeguard has opened. - Robot number executing motion command Controller status
25 Robot setting has changed. - 1: New addition Robot number
2: Change
3: Delete
26 Alarm setting has changed. - Alarm number
27 Safety Board issued a Main stop signal. Check the stop signal from Note 1,2. On system history, If an unintended stop occured.

Type of stop signal

Refer to the "Details of Note Information".

Details of stop signal
- Safety switch
- Axis
- Parts
- Safety input channels
- Deceleration error details
Refer to the "Details of Note Information".
28 Safety Board issued a Sub stop signal. Check the stop signal from Note 1,2. On system history, If an unintended stop occured.

Type of stop signal

Refer to the "Details of Note Information".

Details of stop signal

- Safety switch

- Axis

- Parts

- Safety input channels

- Deceleration error details

Refer to the "Details of Note Information".

50 The battery alarm for the controller was reset. -
51 The battery alarm for the robot was reset. - Robot number
52 The grease alarm for the robot was reset. - Robot number
100 Device connected to Controller. -
101 Console device has changed. -

20: TP3

21:RC+

22:Remote I/O

26: Remote Ethernet

29: Remote RS232

102 Display device has changed. -
103 Working mode has changed. -
104 Cooperative mode has changed. -

0: Independent

1: Cooperative

110 Controller firmware has been installed. -

1: Setup

2: Initialize

3: Upgrade

4: Recover

111 IP address has been restored. May store this log when the controller firmware is installed.
112 Controller rebooted -
113 Communication was restored from the busy state. -
120 RC+ connected to the Controller. -

1: Ethernet

2: USB

121 TP connected to the Controller. -
123 RC+ disconnected from the Controller. -
124 TP disconnected from the Controller. -
126 Working mode changed to AUTO. -
127 Working mode changed to Program. -
128 Working mode changed to Teach. -
129 Remote Ethernet connected to the Controller -
130 Remote Ethernet disconnected to the Controller -
131 Remote Com connected to the Controller -
132 Remote Com disconnected to the Controller -

Logout status

0: Normal

1: Abnormal (Time-out)

133 Working mode changed to Test. -
134 Epson RC+ Express Edition connected to the Controller.
135 Epson RC+ Express Edition disconnected from the Controller.
400

The battery alarm for the controller occurred.

Replace the battery and reset the alarm.

Replace the battery.

After replacing the battery, reset the alarm in Epson RC+ 8.0-[Tools]-[Controller]-[Maintenance].

401

The battery alarm for the robot occurred.

Replace the battery and reset the alarm.

Replace the battery.

After replacing the battery, reset the alarm in Epson RC+ 8.0-[Tools]-[Controller]-[Maintenance].

Robot number
402

The grease alarm occurred.

Grease the robot and reset the alarm.

Grease the robot and reset the alarm.

After greasing up, reset the alarm in Epson RC+ 8.0-[Tools]-[Controller]-[Maintenance].

Robot number
410

The battery alarm for the controller occurred.

Replace the battery and reset the alarm.

Replace the battery.

After replacing the battery, reset the alarm in Epson RC+ 8.0-[Tools]-[Controller]-[ Maintenance].

1000 times of consumption rate 1000 times of boundary value
411

The battery alarm for the robot occurred.

Replace the battery and reset the alarm.

Replace the battery.

After replacing the battery, reset the alarm in Epson RC+ 8.0-[Tools]-[Controller]-[ Maintenance].

1000 times of consumption rate 1000 times of boundary value
412

The belt alarm occurred.

Replace the belt and reset the alarm.

Replace the timing belt.

After replacing the timing belts, reset the alarm in Epson RC+ 8.0-[Tools]-[Controller]-[Maintenance].

1000 times of consumption rate 1000 times of boundary value
413

The grease alarm for the ball screw spline occurred.

Grease the ball screw spline and reset the alarm.

Grease up the ball screw spline.

After greasing up, reset the alarm in Epson RC+ 8.0-[Tools]-[Controller]-[Maintenance].

1000 times of consumption rate 1000 times of boundary value
414

The motor alarm occurred.

Replace the motor and reset the alarm.

Replace the motor.

After replacing the motor, reset the alarm in Epson RC+ 8.0-[Tools]-[Controller]-[Maintenance].

1000 times of consumption rate 1000 times of boundary value
415

The gear alarm occurred.

Replace the gear units and reset the alarm.

Replace the gear units.

After replacing the gear units, reset the alarm in Epson RC+ 8.0-[Tools]-[Controller]-[Maintenance].

1000 times of consumption rate 1000 times of boundary value
416

The ball screw spline alarm occurred.

Replace the ball screw spline and reset the alarm.

Replace the ball screw spline.

After replacing the ball screw spline, reset the alarm in Epson RC+ 8.0-[Tools]-[Controller]-[Maintenance].

1000 times of consumption rate 1000 times of boundary value
420

The battery alarm for the controller occurred.

Replace the battery and reset the alarm.

Replace the battery.

After replacing the battery, reset the alarm in Epson RC+ 8.0-[Tools]-[Controller]-[ Maintenance].

1000 times of consumption rate 1000 times of boundary value
421

The battery alarm for the robot occurred.

Replace the battery and reset the alarm.

Replace the battery.

After replacing the battery, reset the alarm in Epson RC+ 8.0-[Tools]-[Controller]-[ Maintenance].

1000 times of consumption rate 1000 times of boundary value
422

The belt alarm occurred.

Replace the belt and reset the alarm.

Replace the timing belt.

After replacing the timing belts, reset the alarm in Epson RC+ 8.0-[Tools]-[Controller]-[Maintenance].

1000 times of consumption rate 1000 times of boundary value
423

The grease alarm for the ball screw spline occurred.

Grease the ball screw spline and reset the alarm.

Grease up the ball screw spline.

After greasing up, reset the alarm in Epson RC+ 8.0-[Tools]-[Controller]-[Maintenance].

1000 times of consumption rate 1000 times of boundary value
424

The motor alarm occurred.

Replace the motor and reset the alarm.

Replace the motor.

After replacing the motor, reset the alarm in Epson RC+ 8.0-[Tools]-[Controller]-[Maintenance].

1000 times of consumption rate 1000 times of boundary value
425

The gear alarm occurred.

Replace the gear units and reset the alarm.

Replace the gear units.

After replacing the gear units, reset the alarm in Epson RC+ 8.0-[Tools]-[Controller]-[Maintenance].

1000 times of consumption rate 1000 times of boundary value
426

The ball screw spline alarm occurred.

Replace the ball screw spline and reset the alarm.

Replace the ball screw spline.

After replacing the ball screw spline, reset the alarm in Epson RC+ 8.0-[Tools]-[Controller]-[Maintenance].

1000 times of consumption rate 1000 times of boundary value
501 Trace history is active. Effects system performance if trace history is active.
502 Memory has been initialized.

When this error occurs, the value of the Global Preserve variable will be initialized.

Replace the CPU board battery.

Replace the CPU board.

After CPU replacement, if the warning is displayed at the first startup, reboot the Controller.

503 Found Hard disk error. You should replace the hard disk ASAP. This is a warning of the hard disk failure. Replace the hard disk as soon as possible.
504 An Error occurred on a Background Task. Make sure there are no problems in the system and continue the operation.
505 Controller was rebooted.
506 The alarm information is not set. Set the alarm information on [Tools]-[Controller Tools]-[Alarm]. Set the alarm information on [Tools]-[Controller Tools]-[Alarm].
507 The controller is started by using the previous initial setting file since the initial setting file is corrupted. Setting changes from the previous start may not be saved. Please check the settings.
510 Optimized SRAM Data. -
511

Battery voltage of the CPU board backup is lower than the allowed voltage.

Replace the CPU board battery.

Replace the CPU board battery immediately. Keep the power to the controller ON as far as possible until you replace the battery. 100 times of current value 100 times of boundary value
512 5V input voltage for the CPU board is lower than the allowed voltage. If normal voltage is not generated by 5V power supply alone, replace the power supply. 100 times of current value 100 times of boundary value
513 24 V input voltage for the motor brake, encoder and fan is lower than the specified voltage. If normal voltage is not generated by a 24V power supply alone, replace the power supply. 100 times of current value 100 times of boundary value
514 Internal temperature of the Controller is higher than the specified temperature.

Stop the controller as soon as possible and check whether the ambient temperature of the controller is not high.

Check whether the filter is not clogged up.

100 times of current value 100 times of boundary value
515 Rotating speed of the controller fan is below the allowed speed. (FAN1) Check whether the filter is not clogged up. If the warning is not cleared after the controller is rebooted, replace the fan. Current value Boundary value
516 Speed of the controller fan is below the specified speed. (FAN2) Check whether the filter is not clogged up. If the warning is not cleared after the controller is rebooted, replace the fan. Current value Boundary value
517 Internal temperature of the Controller is higher than the specified temperature.

Stop the controller as soon as possible and check whether the ambient temperature of the controller is not high.

Check whether the filter is not clogged up.

100 times of current value 100 times of boundary value
518 54V input voltage for the CPU board is lower than the allowed voltage. If normal voltage is not generated by 54V power supply alone, replace the power supply. 100 times of current value 100 times of boundary value
519 3.3V input voltage for the CPU board is lower than the allowed voltage. If normal voltage is not generated by 3.3V power supply alone, replace the power supply. 100 times of current value 100 times of boundary value
520 DC input voltage for CPU board is lower than or bigger than the specified voltage. If normal voltage is not generated by DC power supply alone, replace the power supply. 100 times of current value 100 times of boundary value
521 DU1 3.3V input voltage for the board is lower than the allowed voltage. If normal voltage is not generated by 3.3V of Drive Unit 1 power supply alone, replace the power supply. 100 times of current value 100 times of boundary value
522 DU1 5V input voltage for the board is lower than the allowed voltage. If normal voltage is not generated by 5V of Drive Unit 1 power supply alone, replace the power supply. 100 times of current value 100 times of boundary value
523 DU1 24 V input voltage for the motor brake, encoder and fan is lower than the specified voltage. If normal voltage is not generated by 24V of Drive Unit 1 power supply alone, replace the power supply. 100 times of current value 100 times of boundary value
524 DU1 Internal temperature of the Controller is higher than the allowed temperature.

Stop Drive Unit 1 as soon as possible and check whether the ambient temperature of Drive Unit 1 is not high.

Check whether the filter is not clogged up.

100 times of current value 100 times of boundary value
525 DU1 Rotating speed of the controller fan is below the allowed speed. (FAN1) Check whether the filter of Drive Unit 1 is not clogged up. If the warning is not cleared after the controller is rebooted, replace the fan. Current value Boundary value
526 DU1 Rotating speed of the controller fan is below the allowed speed. (FAN2) Check whether the filter of Drive Unit 1 is not clogged up. If the warning is not cleared after the controller is rebooted, replace the fan. Current value Boundary value
531 DU2 3.3V input voltage for the board is lower than the allowed voltage. If normal voltage is not generated by 3.3V of Drive Unit 2 power supply alone, replace the power supply. 100 times of current value 100 times of boundary value
532 DU2 5V input voltage for the board is lower than the allowed voltage. If normal voltage is not generated by 5V of Drive Unit 2 power supply alone, replace the power supply. 100 times of current value 100 times of boundary value
533 DU2 24 V input voltage for the motor brake, encoder and fan is lower than the specified voltage. If normal voltage is not generated by 24V of Drive Unit 2 power supply alone, replace the power supply. 100 times of current value 100 times of boundary value
534 DU2 Internal temperature of the Controller is higher than the allowed temperature.

Stop Drive Unit 2 as soon as possible and check whether the ambient temperature of Drive Unit 2 is not high.

Check whether the filter is not clogged up.

100 times of current value 100 times of boundary value
535 DU2 Rotating speed of the controller fan is below the allowed speed. (FAN1) Check whether the filter of Drive Unit 2 is not clogged up. If the warning is not cleared after the controller is rebooted, replace the fan. Current value Boundary value
536 DU2 Rotating speed of the controller fan is below the allowed speed. (FAN2) Check whether the filter of Drive Unit 2 is not clogged up. If the warning is not cleared after the controller is rebooted, replace the fan. Current value Boundary value
541 DU3 3.3V input voltage for the board is lower than the allowed voltage. If normal voltage is not generated by 3.3V of Drive Unit 3 power supply alone, replace the power supply. 100 times of current value 100 times of boundary value
542 DU3 5V input voltage for the board is lower than the allowed voltage. If normal voltage is not generated by 5V of Drive Unit 3 power supply alone, replace the power supply. 100 times of current value 100 times of boundary value
543 DU3 24 V input voltage for the motor brake, encoder and fan is lower than the specified voltage. If normal voltage is not generated by 24V of Drive Unit 3 power supply alone, replace the power supply. 100 times of current value 100 times of boundary value
544 DU3 Internal temperature of the Controller is higher than the allowed temperature.

Stop Drive Unit 3 as soon as possible and check whether the ambient temperature of Drive Unit 3 is not high.

Check whether the filter is not clogged up.

100 times of current value 100 times of boundary value
545 DU3 Rotating speed of the controller fan is below the allowed speed. (FAN1) Check whether the filter of Drive Unit 3 is not clogged up. If the warning is not cleared after the controller is rebooted, replace the fan. Current value Boundary value
546 DU3 Rotating speed of the controller fan is below the allowed speed. (FAN2) Check whether the filter of Drive Unit 3 is not clogged up. If the warning is not cleared after the controller is rebooted, replace the fan. Current value Boundary value
550 Communication with the Compact Vision is disconnected. Check the network wiring. Check the connection between the controller and the compact vision. Camera No.
551 Compact Vision CPU fan RPM has decreased. Clean the fan filter and / or replace the fan.

Check whether the fan filter of the compact vision is not clogged up.

If the warning is not cleared after the controller and the compact vision are rebooted, replace the CPU fan.

Camera No. Current value
552 Compact Vision CPU fan RPM has decreased. Clean the fan filter and / or replace the fan. Replace the CPU fan of the compact vision. Camera No. Current value
553 Compact Vision chassis fan RPM has decreased. Replace the fan.

Check whether the fan filter of the compact vision is not clogged up.

If the warning is not cleared after the controller and the compact vision are rebooted, replace the system fan.

Camera No. Current value
554 Compact Vision chassis fan RPM has decreased. Replace the fan. Replace the system fan of the compact vision. Camera No. Current value
555 Compact Vision CPU temperature is too high. Check the installation environment (ventilation, ambient temperature, etc.)

Check whether the fan filter of the compact vision is not clogged up.

If the warning is not cleared after the controller and the compact vision are rebooted, check the installation environment (surrounding space, ambient temperature) of the compact vision.

Camera No. 100 times of current value
556 Compact Vision CPU temperature is too high. Check the installation environment (ventilation, ambient temperature, etc.)

Check whether the fan filter of the compact vision is not clogged up.

If the warning is not cleared after the controller and the compact vision are rebooted, check the installation environment (surrounding space, ambient temperature) of the compact vision.

Camera No. 100 times of current value
557 Compact Vision backup battery voltage is low. Replace the battery. Replace the backup battery of the compact vision. Camera No. 100 times of current value
558 Compact Vision backup battery voltage is low. Replace the battery. Replace the backup battery of the compact vision. Camera No. 100 times of current value
559 Compact Vision process was terminated abnormally. Restart the Compact Vision unit. If the warning is not cleared after the controller and the compact vision are rebooted, initialize the compact vision. Camera No.
560 Compact Vision available memory is low. Restart the Compact Vision unit. If the warning is not cleared after the controller and the compact vision are rebooted, initialize the compact vision. Camera No. Current value
561 Compact Vision available disk space is low. Reduce the number of objects that use models (Geometric, Correlation, DefectFinder, etc.)

Check the vision sequence if it has unnecessary models which can be reduced.

Consider to use the USB memory.

Camera No. Current value
562 A critical hardware error occurred in the Compact Vision unit. Check the hardware condition such as internal wiring. If the warning is not cleared after the controller and the compact vision are rebooted, initialize the compact vision. Camera No.
563 A critical hardware error occurred in the Compact Vision unit. Check the hardware condition such as internal wiring. If the warning is not cleared after the controller and the compact vision are rebooted, replace the LED/SW board. Camera No.
569 Communication with the Compact Vision recovered. - Camera No.
570 Compact Vision. Password authentication has failed.

Enter the correct Compact Vision connection password in the RC+ Camera page.

If the password is unknown, you must do one of the following:

a. Enter a new connection password from CV Monitor, then enter the same password in the RC+ Camera page. or

b. Perform a factory reset on the Compact Vision unit to clear the password. Rebuild the current RC+ project and check operation.

580 OPC UA Server. Server error. Reboot the Controller. OPC UA Status Code (tens digit)
581 OPC UA Server. Server log is activated.

Turn OFF the log function of OPC UA Server.

Reboot the Controller.

582 OPC UA Server. File size of the server log is exceeded.

Turn OFF the log function of OPC UA Server.

Reboot the Controller.

590 Detect the different of the calibration settings in the controller and Safety Board.

Do one of the following and reboot the Controller:

- Execute calibration from the Controller settings.

- Correct the settings of the Safety Board from the Safety Function Manager.

Axis number detected the difference at first. Pulse value of the axis detected the difference at first.
597 The PTP motion to avoid the singularity point has completed.

PTP motion for the singularity avoidance was completed.

Clicking the same jog button will operate the robot in the normal jog motion.

598 Robot stopped due to collision detection Move the manipulator to the direction avoiding collision
599 Jogging attempted near singularity point.

The robot could not jog in the CP motion (default).

Clicking the same jog button will operate the robot in the PTP motion.

700 Motor driver type does not match the current robot model. Check the robot model. Replace the motor driver.
736 Encoder is reset. Reboot the controller. Reboot the controller.
737

Low voltage from the encoder battery.

Replace the battery.

Turn OFF the controller and replace the battery. For the battery replacement procedure, refer to Maintenance in the Manipulator manual. Replace the CPU board. Check the connection of the cable.
752 Servo alarm D. -