LED Description
For the PROFINET IO Controller protocol, the system status LED SYS, communication LED SF (System Failure), BF (Bus Failure), ethernet LED Link or RX/TX can assume the states described below.
| SYS | SF | BF | Meaning |
|---|---|---|---|
| System status Yellow/green | System Failure COM0 red/green | Bus Failure COM1 red/green | LED name General LED name Colors of the SYS and SF LEDs, or of BF |
| Firmware and Configuration | |||
| The power supply to the device is missing or hardware may have faults. | |||
| No second stage bootloader found in Flash memory. | |||
Green/yellow, cyclic | No firmware file found in Flash file system. | ||
| PROFINET IO Controller is not configured | |||
| No Ethernet port has a link. E.g., no cable is connected to any of the Ethernet ports. | |||
| PROFINET IO Controller is not online (the bus is turned OFF). | |||
| PROFINET communication | |||
or On, red | Not all configured devices are in data exchange. | ||
| - | One IO Device connected to the PROFINET IO Controller reports a problem. | ||
| All configured devices are in data exchange. No problem has been reported by any device. | |||
| PROFINET IO Controller operation | |||
| PROFINET DCP Set Signal has been received. | |||
| The PROFINET IO Controller has detected an address conflict. Another device in the network is using the same Station name or IP address as the PROFINET IO Controller. This could also be a Watchdog error. | |||
| No valid Master license | |||
| LED | Color | State | Meaning |
|---|---|---|---|
| LINK Ch0 & Ch1 | LED green | ||
| ON | The device is linked to the Ethernet. | ||
| OFF | The device has no link to the Ethernet. | ||
| RX/TX Ch0 & Ch1 | LED yellow | ||
| Flickering (load dependent) | The device sends/receives Ethernet frames. | ||
| OFF | The device does not send/receive Ethernet frames. | ||
| LED state | Description |
|---|---|
| Blinking (1 Hz, 3 s) | The indicator turns on and off for 3 seconds with a frequency of 1 Hz: "on" for 500 ms, followed by "off" for 500 ms. |
| Blinking (1 Hz) | The indicator turns on and off with a frequency of 1 Hz: "on" for 500 ms, followed by "off" for 500 ms. |
| Blinking (2 Hz) | The indicator turns on and off with a frequency of 2 Hz: "on" for 250 ms, followed by "off" for 250 ms. |
| Flickering (load dependent) | The indicator turns on and off with a frequency of approximately 10 Hz to indicate high Ethernet activity: "on" for approximately 50 ms, followed by "off" for 50 ms. The indicator turns on and off at irregular intervals to indicate low Ethernet activity. |
← Specification Modes →