Slave Communication Error Detection / Busoff Detection / Not-added

Number Master LED Condition MS NS
Green Light ON Red Light Blinking
1 Absent Slave LED Condition Green Light ON Red Light Blinking
2 Absent Slave LED Condition (Busoff detection) Green Light ON Red Light ON
3 Absent Slave LED Condition Green Light ON Light OFF

Process Flowchart

* See also:

Symbol See also:
1 Disconnected Terminating Resistors, Cable Disconnection, Disconnected Connector, and Disconnected Signal Wire
2 Loose Connector and Signal Wire
3 Noise Intrusion

Causes of Error

Possible Cause Examination Method Countermeasure
  • Disconnected terminating resistors
  • Cable disconnection
  • Disconnected connector
  • Disconnected signal wire
Check that terminating resistors are connected to both ends of the network.

Measure resistance between signal wires with communications power supply OFF.

→ Normal: 50 to 70 Ω

Measuring point: Connection of the problem unit

See also: Disconnected Terminating Resistors, Cable Disconnection, Disconnected Connector, and Disconnected Signal Wire

Fix the problem.

How to find the trouble point:

Remove the terminating resistor on one end of the network.

The trouble point is where resistance changes from 120 Ω.

  • Loose connector
  • Loose signal wire
Check for the connection of connectors and signal wires.

→ The connectors and signal wires should be firmly connected.

Checkpoint: Checkpoint: all nodes and all branch taps

See also: Loose Connector and Signal Wire

Connect the connectors and signal wires again.
Voltage drop of communications power supply Measure voltage of communications power supply at the unit with a trouble.

→ Normal: 11V or more between V+ and V-

If the voltage is 11 to 14 V, the unit is a possible cause. Fix the problem on the unit.

Check the voltage of the power supply.

Calculate the current capacity of the cable and add more communications power supplies.

Noise (external cause) Check the noise intrusion via the following paths (1) to (3).
  • Noise via DRAIN (FG)
  • Induced noise via communication cable
  • Communications power supply
  • See also: Noise Intrusion

    Take countermeasures against noise.
    Broken unit Replace the trouble unit with a new one.

    → Verify whether the problem is fixed.

    Replace the unit with a new one.
    No cause is identified.

    Identify the trouble point by dividing the network.

    See also: Broken Unit Examination (Dividing Network Examination)