Slave: Data Link Error

MS NS
Master LED Condition Light OFF Red Light Blinking
Absent Slave LED Condition

(Data link error)

Light OFF Red Light ON

Process Flowchart

* See also:

Symbol See also:
1 Disconnected Terminating Resistors, Cable Disconnection, Disconnected Connector, and Disconnected Signal Wire
2 Loose Connector and Signal Wire
3 Noise Intrusion

Causes of Error

Possible Cause Examination Method Countermeasure
  • Disconnected terminating resistors
  • Cable disconnection
  • Disconnected connector
  • Disconnected signal wire
  1. Check that terminating resistors are connected to both ends of the network.
  2. Measure resistance between signal wires with device power supply OFF.

    → Normal: 100 to 120 Ω

Fix the problem.

How to find the trouble point:

Remove the terminating resistor on one end of the network.

The trouble point is where resistance changes from 220 Ω.

  • Loose connector
  • Loose signal wire
Check for the connection of connectors and signal wires.

→ The connectors and signal wires should be firmly connected.

Connect the connectors and signal wires again.
Noise (external cause)

Check the noise intrusion via the following paths (1) to (3).
  • Noise via shield
  • Induced noise via communication cable
  • Device power supply

    → See also: Noise Intrusion

  • Take countermeasures against noise.
    Broken unit Replace the trouble unit with a new one.

    → Verify whether the problem is fixed.

    Replace the unit with a new one.
    No cause is identified. Identify the trouble point by dividing the network.

    → See also: Broken Unit Examination (Dividing Network Examination)

    -