Editing of Input / Output Size

You can change the input/output size of the EtherCAT slave module. Change the input/output size as necessary.

  1. Select [Setup] - [System Configuration] and display the [System Configuration] dialog box.

  2. Select [Controller] - [Inputs / Outputs] - [Fieldbus Slave] - [General].

  3. Change the settings of [Input Byte] and [Output Byte].
    In this example, both of them are changed to "20" Bytes.

KEY POINTS


Cautions when connecting OMRON PLC and this option:

The input/output size has limitations.

Select any of 32 bytes, 64 bytes, 128 bytes, or 256 bytes for both [Input Bytes] and [Output Bytes].

[Input Bytes] and [Output Bytes] may have a different size.

  1. Click [Apply].

  2. Click [Close].
    The following dialog box appears and the Controller automatically starts rebooting.

  3. Select [Setup] - [System Configuration] and display the [System Configuration] dialog box.

  4. Select [Controller] - [Inputs / Outputs].

  5. Confirm that the following items are displayed in "Fieldbus Slave".
    Inputs: "512" - "512 + Changed number of input I/O (Bits)"
    Outputs: "512" - "512 + Changed number of output I/O (Bits)"
    In this example, Input byte is 20 bytes (160 bits) and "512 - 671" is displayed in Inputs.
    Also, Output byte is 20 bytes (160 bits) and "512 - 671" is displayed in Outputs.

  6. Click [Close].