Specification

Item Specification
Name PROFIBUS-DP slave module
Connection Method Hybrid (token passing procedure and master-slave communication)
Baud Rates 9.6 k, 19.2 k, 45.45 k, 93.75 k, 187.5 k, 500 k,

1.5 M, 3 M, 6 M, 12 M (bps)

Transfer Distance Baud Rates Cable Length
12 Mbps 100 m
6 Mbps 100 m
3 Mbps 100 m
1.5 Mbps 200 m
500 kbps 400 m
187.5 kbps 1000 m
93.75 kbps 1200 m
45.45 kbps 1200 m
19.2 kbps 1200 m
9.6 kbps 1200 m
Maximum Stations 126 (including master unit and repeater)
Data Length / Frame 244 bytes
Cable 2-wire cables dedicated to PROFIBUS (2 wires for signal)
Modes Slave
Interface 1 PROFIBUS-DP port (EN 50170)
Output Current Capacity Maximum 100 mA
Max. Input data size 1952 bit (244 bytes)
Max. Output data size 1952 bit (244 bytes)