Network Cable

The PROFIBUS cable can be used as a network cable.
There are four types (A, B, C, and D) of PROFIBUS cables. Normally, cable type A is used for PROFIBUS DP network. The cable type A specifications are shown in the table below.

Item Specification
Impedance 135 to 165 Ω
Capacity < 30 pf/m
Loop resistance 110 Ω/km
Wire diameter 0.64 mm
Core cross-section > 0.34 mm2

It is recommended to use a 9-pin D-Sub connector for protecting rating IP 20. For IP 65/67, M12 connector (IEC 947-5-2 compliant), Han-Bird connector (DESINA compliant), and Siemens hybrid connector are available.

Pin assignment (9-pin D-Sub)

Pin No. Signal Assignment
1 Shield Shield/Protective ground
2 M24 Ground of output voltage (24 V)
3 RxD/TxD-P Data line B
4 CNTR-P Repeater control signal (directional control)
5 DGND Communications power supply (5 V)
6 VP Supply voltage to terminating resistor (P5V)
7 P24 Output voltage (24 V)
8 RxD/TxD-N Data line A
9 CNTR-N Repeater control signal (directional control)

Use pins 2 and 7 for connecting a maintenance device without any power supply.

The following figure illustrates wiring sample.

PROFIBUS cables are produced by a variety of manufacturers.

For details of the PROFIBUS cables, see PROFIBUS International’s website: