LED Description

LED state represents the status of the fieldbus board.

  • SYS: System Status LED

    LED State Description
    Green Operating in normal condition
    Flashing Green/Yellow Waiting for firmware to load
    Yellow Waiting for firmware (netX) to load
    OFF The power supply to the device is missing or hardware may have faults.
  • MNS: Module Network Status LED

    For the DeviceNet Master protocol, the communication status LED MNS can assume the states described below.

    LED Color State Description
    MNS Duo LED red/green
    (Green) ON Device operational and on-line, connected:

    Device is online

    Connections with all slaves are established.

    (Green) Flashing

    (1 Hz)

    Device operational and on-line:

    Device is online, No connection is established.

    Configuration missing, incomplete or incorrect

    (Green, Red, OFF) Flashing

    (2 Hz)

    Green, Red, OFF

    Self test after power ON.
    (Red) Flashing

    (1 Hz)

    Minor fault and/or connection time-out:

    Device is online

    One or more connections are established

    Device has data exchange with at least one of the configured slaves or no data exchange with one of the configured slaves.

    (Red) ON Critical fault or critical link failure:

    Critical connection failure

    Device has detected a network error. Duplicate MAC-ID or severe error in CAN network.

    (OFF) OFF Device is not powered
    • The device may not be powered.
    • Device is not on-line and/or no network power
    • The device has not yet complete the Dup_MAC_ID test.
    • The device is powered.

      The network power is missing.

    LED State Description
    Flashing

    (1 Hz)

    The indicator turns ON and OFF with a frequency of approx. 1 Hz.

    Turn ON for 500 ms, followed turn OFF for 500 ms.

    Flashing

    (2 Hz)

    Green, Red, OFF
    The indicator turns to green on for 250 ms, and red on for 250 ms, then turn OFF.