Trunk Line and Drop Line
Trunk line is a backbone cable of DeviceNet network with terminating resistors on the both ends.
Drop line is a branch of the trunk line.
For DeviceNet, 5-wire cables are used for trunk lines and drop lines. Commercially available DeviceNet cables can be used. There are two types of DeviceNet cables: Thick cable and Thin cable. Environment-resistant cable and flexible cable are available.
For details, see the website of ODVA.
https://www.odva.org/ (opens new window)
Thick Cable
Symbol Description a 11.2 mm to 12.1 mm outside diameter b Shield Wire c Power Wire (Red/Black) d Signal Wire (Blue/White) e Braid Shield Thin Cable
Symbol Description a 6.9 mm outside diameter b Shield Wire c Power Wire (Red/Black) d Signal Wire (Blue/White) e Braid Shield
Communications Cable Signal
| Wire Type | Color | Details of Signal | Wire Identity | |
|---|---|---|---|---|
| Signal wire | Blue | Signal | Low | CAN L |
| White | Signal | High | CAN H | |
| Power wire | Red | Communications power supply | + Positive | V+ |
| Black | Communications Power Supply | − Negative | V− | |
| Shield Wire | - | Shield | S | |