Trunk Line and Drop Line

Trunk line is a backbone cable of DeviceNet network with terminating resistors on the both ends.

Drop line is a branch of the trunk line.

For DeviceNet, 5-wire cables are used for trunk lines and drop lines. Commercially available DeviceNet cables can be used. There are two types of DeviceNet cables: Thick cable and Thin cable. Environment-resistant cable and flexible cable are available.

For details, see the website of ODVA.
https://www.odva.org/ (opens new window)

  • Thick Cable

    Symbol Description
    a 11.2 mm to 12.1 mm outside diameter
    b Shield Wire
    c Power Wire (Red/Black)
    d Signal Wire (Blue/White)
    e Braid Shield
  • Thin Cable

    Symbol Description
    a 6.9 mm outside diameter
    b Shield Wire
    c Power Wire (Red/Black)
    d Signal Wire (Blue/White)
    e Braid Shield

Communications Cable Signal

Wire Type Color Details of Signal Wire Identity
Signal wire Blue Signal Low CAN L
White Signal High CAN H
Power wire Red Communications power supply + Positive V+
Black Communications Power Supply − Negative V−
Shield Wire - Shield S