Confirmation and Configuration of Epson RC+ 8.0
When the EtherNet/IP slave module is installed to the Controller, it is recognized automatically. Confirm that Epson RC+ 8.0 has recognized the module in the following procedure.
Select [Setup] - [System Configuration] and display the [System Configuration] dialog box.
Select [Controller] - [Inputs / Outputs].
Confirm that the following items are displayed in "Fieldbus slave".
Installed: Yes
Inputs: 512-767 (default setting)
Outputs: 512-767 (default setting)Select [Fieldbus Slave] - [General]
Confirm that following items are displayed.
Fieldbus Type: EtherNet/IP
Input Bytes: 32 (default setting)
Output Bytes: 32 (default setting)Click [Close].
Select [Fieldbus Slave] - [EtherNet/IP].
Set each item to the specific value to connect the Ethernet network.
For information about the setting values, contact your network administrator.
Address Configuration is set to "DHCP/BOOTP/ARP" at shipment.When the configuration is completed, click [Apply] to apply the setting.
Click [Close].
KEY POINTS
When Address Configuration is set to "DHCP/BOOTP/ARP", the Controller waits for DHCP/BOOTP/ARP sever response for 30 seconds at Controller startup. When DHCP/BOOTP/ARP does not respond within the time, the Controller stops the request to the DHCP/BOOTP/ARP server and waits ARP.